Protected Membrane Roofs, Green Roofs and Rooftop Solar on Calgary Flat Roofs

A protected membrane roof puts insulation and ballast over the membrane, a green roof adds growing medium and plants, and a solar array adds racks, ballast or penetrations. Because each adds weight, each needs a structural engineer's review. A PMR also needs a 2% minimum slope, and the membrane is leak tested before anything covers it.

Quick facts

  • PMR slope: minimum 2% (1:50, or 1/4 in per ft) for every protected membrane roof.
  • PMR insulation: only closed cell extruded polystyrene meeting Type 4 under CAN/ULC-S701 is accepted.
  • Thermal cycling: a bare roof surface can vary by 55 C (130 F) in a day and 110 C (230 F) or more in a year.
  • Green roof weight: 48.8 to 170.9 kg/m2 (10 to 35 lb/ft2) saturated for extensive roofs with 150 mm (6 in) or less of growing medium; up to 1,464.7 kg/m2 (300 lb/ft2) for intensive roofs.
  • Ballast: at least 50 kg/m2 (10 lb/ft2) on the field and 60 kg/m2 (12 lb/ft2) at perimeters, corners and penetrations for SOPRA-XPS 50 mm (2 in) and thinner.
  • Stormwater: SOPRARETENTIO BOARD holds up to 21.6 L/m2 (0.53 US gal/ft2) of rain with no growing medium on it.
  • Flood testing: not recommended for roofs; 50 mm (2 in) of water over a 15 m basin sloped at 2% averages about 100 kg/m2 (20 lb/ft2).

What is a protected membrane (inverted) roof?

A protected membrane roof, or PMR, places the waterproofing membrane directly on the deck and covers it with insulation and ballast, the reverse of a conventional roof. It is also called the upside down roof. The membrane is the waterproof sheet; ballast is the loose weight, usually stone or pavers, that holds the insulation down.

The gain is easy to see. A roof surface can vary by 55 C (130 F) in a day and by 110 C (230 F) or more in a year.

A membrane under insulation sees only a fraction of that cycling, so its life expectancy increases, and because it sits on the warm side of the insulation it also acts as the vapour retarder.

Only one insulation qualifies: closed cell extruded polystyrene (XPS) meeting Type 4 under CAN/ULC-S701, because the board must resist water, UV, freeze-thaw and compression.

Soprema's SOPRA-XPS 35 carries that rating as CAN/ULC S701.1 Type 4 (ASTM C578-14 Type IV) with a minimum compressive strength of 241 kPa (35 psi). The SOPRA-XPS 35 DC version adds drainage grooves underneath so water reaches the drains instead of floating the boards.

Burying the membrane under insulation spares it most of the daily and yearly temperature swing, and that is the main case for an inverted roof. The cost is paid in ballast, which makes weight the next question.

How much weight do these systems add?

Weight is the first number to settle. The structural capacity of the deck matters most in choosing a green roof type, and a qualified structural engineer must evaluate any existing roof first. Green roofs are sorted by depth and saturated weight.

Extensive roofs carry 150 mm (6 in) or less of growing medium and weigh 48.8 to 170.9 kg/m2 (10 to 35 lb/ft2); intensive roofs carry more than 150 mm and weigh 170.9 to 1,464.7 kg/m2 (35 to 300 lb/ft2), with semi-intensive roofs in between.

Designers should then assume supersaturation, with drains plugged and water standing as high as the overflow scuppers. Water weighs 1,000 kg/m3, so 50 mm (2 in) of it adds 50 kg/m2 (10 lb/ft2) before any soil is counted, and snow, wind, rain and people are live loads added to that.

Lighter products narrow the range. Soprema's SOPRANATURE SEDUM MATS come as a regular pre-grown mat at 29.3 to 39.2 kg/m2 (6 to 8 psf) saturated and an ultra light mat at 9.8 to 14.6 kg/m2 (2 to 3 psf). PMR ballast is its own load.

Soprema requires at least 50 kg/m2 (10 lb/ft2) on the field and 60 kg/m2 (12 lb/ft2) at perimeters, corners and penetrations for SOPRA-XPS 50 mm (2 in) and thinner, rising past 200 kg/m2 (42 lb/ft2) for 200 mm (8 in) boards.

There is no published weight per solar panel, but snow drifts against the back of tilted modules and adds load.

The semi-intensive band is listed at 170.9 to 244.1 kg/m2 (35 to 50 lb/ft2) saturated. The weight of a growing medium is always specified at its maximum water retention capacity per unit of depth, so that is the figure to ask your supplier for.

What does rooftop solar do to a flat roof warranty?

Adding a solar array without the prior consent of the roofing contractor or roofing system manufacturer may increase warranty costs or void the roof warranty entirely. A manufacturer-approved roofing contractor should verify the roof before PV work starts, the roofer and manufacturer should be present during installation, and a thorough roof inspection should follow.

Roof age matters as much as consent. It makes no sense to install a thirty-year PV system on a roof with five or ten years of service life left, because the array may have to come off when the roof is replaced.

Securement is the other warranty question. Installers use three mounting methods: penetrations to structural framing, ballast, or a hybrid. Ballast avoids penetrations but adds weight and limits tilt.

Panels should be listed to UL 1703, which references the UL 790 fire test, similar to CAN/ULC-S107-10 in the National Building Code. The CSA dynamic wind uplift test for membrane roofs has also been used to rate PV systems.

Three systems compared: what sits on the membrane and what it demands

Item Protected membrane roof Green roof Rack-mounted solar
Layers above the membrane XPS insulation, filter layer or drainage board, ballast Root barrier where needed, drainage layer, filter layer, growing medium, plants Racks on structural penetrations, ballast or both
Added weight Ballast from 50 kg/m2 (10 lb/ft2) for XPS 50 mm and thinner 48.8 to 1,464.7 kg/m2 (10 to 300 lb/ft2) saturated Not published; array, racking, ballast and drifted snow all add load
Drainage and checks 2% minimum slope; engineer confirms load capacity Drainage layer required; structural engineer; leak test before covering Must not impede drainage; carrying capacity verified; roof inspected after installation

What changes under the insulation with SBS, EPDM, PVC, TPO or built-up roofing

The layers above the membrane barely change; the membrane under them does. All five protected membrane specifications lay the extruded polystyrene loose on the finished membrane with staggered joints, taper it into 600 mm by 600 mm (24 in by 24 in) sumps at drains where possible, and lay only as much insulation as can take filter fabric and ballast the same day.

On a steel deck, every one of them needs a support panel under the membrane.

SBS modified bitumen EPDM PVC TPO Built-up (BUR)
Membrane under the insulation Base sheet self-adhered, mopped, torched or in cold adhesive; cap sheet torched, in cold adhesive or in 1.0 to 1.5 kg/m2 (0.2 to 0.3 lb/ft2) of hot asphalt Sheet 1.1 to 2.2 mm (45 to 90 mil) in bonding adhesive, or fleeceback in Type III asphalt or SEBS bitumen at 1 to 1.5 kg/m2; taped seams Fibreglass-reinforced sheet 1.2 to 2.4 mm (48 to 96 mil) in adhesive, or feltback sheet with no adhesive on its back; all seams hot-air welded Reinforced sheet 1.1, 1.5 or 2.0 mm (45, 60 or 80 mil) in adhesive, or fleeceback in hot asphalt or SEBS bitumen; all seams hot-air welded Four plies of No. 15 organic felt mopped at 1 kg/m2 (0.2 lb/ft2), or Type IV or VI glass felt at 1.2 kg/m2 (0.25 lb/ft2)
Insulation XPS, CAN/ULC S-701 Type 4 XPS Type 4 with provision for drainage channels XPS Type 4 XPS Type 2, 3 or 4, as the membrane maker approves XPS Type 4
Between membrane and XPS Not stated Not stated Approved separation layer, except under fleece-backed sheet Not stated Not stated
Filter fabric Woven polypropylene, 300 mm (12 in) laps, pieces at least 2.4 m by 2.4 m (8 ft by 8 ft), turned up 75 mm (3 in) above the ballast As SBS As SBS As SBS As SBS
Ballast or pavers Stone to ASTM D 448 gradation #2, 4, 5 or 57; concrete pavers at walkways As SBS As SBS As SBS As SBS, or 50 mm (2 in) pavers up to 16.7% slope, or composite boards with gravel at 27 kg/m2 (5.5 lb/ft2)
Drainage layer Not stated; sumps tapered at drains Channels in the XPS; field splices at least 150 mm (6 in) outside the drain sump Not stated Not stated Not stated
Flashings Two-ply SBS; at upstands the cap sheet goes on in 1 m strips with laps 50 mm (2 in) wider than the base sheet's Cured or self-adhering EPDM at least 200 mm (8 in) high; uncured strips over vertical splices and T-joints No bitumen may touch the PVC; termination bar at 150 to 200 mm (6 to 8 in) along the upper edge; flashings over 750 mm (30 in) high need extra securement As PVC, with TPO-clad metal Four plies of No. 15 felt (glass felt not allowed) or two-ply SBS at least 200 mm (8 in) above the ballast

The real split is bitumen against thermoplastic. SBS and built-up membranes are bonded with hot asphalt, torch or adhesive, while PVC and TPO flashings must never touch bitumen, and PVC needs a separation layer against the polystyrene unless the sheet is fleece-backed.

EPDM and TPO sit in between: either can be a fleeceback sheet mopped into hot asphalt or SEBS bitumen at 1 to 1.5 kg/m2. Hot rubberized asphalt is a sixth option, applied as a hot liquid and always built as a protected membrane.

The TPO specification is the one exception on insulation: it accepts XPS Type 2, 3 or 4, where the general protected membrane rule and the other four specifications name Type 4 only, so the membrane maker's approved list decides. None of the five sets a ballast weight.

Coverage depends on the stone size and gradation and comes from the membrane and insulation makers, ballast must not be stockpiled on the roof, and large paver areas need venting between the insulation and the pavers.

Soprema's boards add two site rules. SOPRA-XPS is laid loose, with any second layer staggered and not glued to the first, and its maximum service temperature is 75 C (167 F); in sun, air trapped between the insulation and drainage panels can overheat the boards, so ballast goes on as the crew lays the panels.

Where pavers or plaza traffic load the insulation, denser boards are made: SOPRA-XPS 40 at 275 kPa (40 psi), 60 at 415 kPa (60 psi) and 100 at 690 kPa (100 psi), against 241 kPa (35 psi) for SOPRA-XPS 35, all CAN/ULC S701.1 Type 4.

How a PMR is built so it drains and stays in place

Slope comes first. Every PMR needs at least 2% (1:50, or 1/4 in per ft), because the insulation does not absorb water readily but any excess must drain quickly. Soprema sets a general floor of 1% (1/8 in per ft) for its roof systems, but 2% is the figure written specifically for a PMR.

Ballast does the holding. A PMR resists wind uplift through the weight on the insulation, which also stops the boards floating in heavy rain, and a filter layer or drainage panel goes down first.

Canada has no standard or test protocol for the wind resistance of a ballasted roof, so designers use the ANSI/SPRI RP-4 calculation, and an engineer confirms the structure can carry the result.

Timing protects the boards. SOPRA-XPS must not be exposed to UV for more than 60 days, so Soprema says not to lay boards the crew cannot cover the same day. Soprema also rules out solvent-based cold adhesives in any system with polystyrene insulation, including a PMR.

A rooftop patio fits this assembly. Pavers can serve as PMR ballast, and Soprema lists paver pedestals and SOPRA-XPS among its SOPRANATURE plaza deck components. Recreational foot traffic is a live load the engineer must include.

A wood-framed deck over a membrane is a separate detail that must come from the membrane manufacturer. A rooftop deck or patio in Calgary needs City approval before it is built.

The City states that a rooftop deck or balcony on a garage or similar building always requires a development permit, with a building permit after it, and the owner should confirm the permits for any other building with the City before design starts.

What a green roof needs under the plants

Every green roof needs a drainage layer, a filter layer, an engineered growing medium and, for most membranes, a root barrier. Any standard membrane type can be used, but it should be upgraded for the life of the garden with more plies, a thicker membrane, better seaming, upgraded flashings or a redundant layer.

Root barriers stop the slow leak. Where a membrane is not inherently root resistant, it needs a separate inorganic sheet of thick polyethylene, rubber or thin copper. That sheet must be seamed over the whole area, including joints, borders and projections, and be UV resistant wherever exposed; Soprema lists SOPRABARRIER 20 and 30 for this role.

Depth thresholds differ between the general industry definitions and Soprema's system, so your quote should name the system by depth, not by label.

Type General growing medium depth Soprema SOPRANATURE substrate depth
Extensive 150 mm (6 in) or less Less than 150 mm of SOPRAFLOR
Semi-intensive Within 25% above or below 150 mm (6 in) 150 mm to 300 mm of SOPRAFLOR
Intensive More than 150 mm (6 in) More than 300 mm of SOPRAFLOR

Test before the membrane is buried. A water impermeability test is required immediately after the crew installs the membrane. Electric Field Vector Mapping (EFVM) is recommended for vegetated roofs because it can find breaches after soil and plants are in place; EFVM does not work on black EPDM.

Stormwater is a design output. SOPRARETENTIO BOARD retains up to 21.6 L/m2 (0.53 US gal/ft2) with no growing medium. At a 2% slope, 100 mm of growing medium removes surface runoff, while flow lengths over 27.7 m may hold water beyond 48 hours. Those figures were worked out for Montreal rainfall and must be recalculated elsewhere.

Soprema's Mammouth SOPRANATURE warranty, available only with its Mammouth Platinum waterproofing warranty, covers replacement of the vegetated components and the labour to remove and reinstall them during an infiltration repair.

The table lists the layers of a green roof, what each one does and the industry requirement or caution that applies to it.

Layer What it does Requirement or caution
Vegetation-free zones Maintenance access, wind and fire breaks, drainage, erosion control and protection for plants, drains and equipment Usually concrete pavers or mineral aggregate; their wind uplift resistance and dead load must be designed for
Growing medium Root zone, nutrient supply and a balance of water and air Lightweight mineral materials such as lava, pumice, expanded clay, expanded schist and clay tiles are the proven base; untreated organic material and topsoil are only additions, because of their weight and drainage
Filter layer Holds the soil in place and keeps fine particles and plant debris out of the drainage layer Sufficient overlaps; carried up vertical edges and secured; matched to the particle size of the growing medium so it does not clog
Moisture retention fabric Stores rain for the plants Holds little compared with the growing medium or a deep profiled drainage board; never laid directly on the insulation of a protected membrane assembly
Drainage layer Carries excess water away and can store some for dry spells Lightweight plastic forms, cellular plastic foam, synthetic fibre mats, granular aggregate, rigid mineral board or profiled drainage boards; must resist degradation and deformation in service
Aeration layer over PMR insulation Lets water drain quickly and moisture evaporate Must be permeable to air and vapour, such as gravel over filter fabric or preformed drainage boards; a vapour-tight layer drives moisture back into the insulation
Insulation Supplies the thermal resistance Must resist creep under continuous load and deformation under point loads; one layer where possible, otherwise the thicker layer underneath

Planting has a calendar. Plants are established by seed, by cuttings (sedum varieties), as root ball plants or as pre-cultivated mats and trays, and the recommended planting periods are early spring, April to June, and late summer, September.

Summer planting needs enough watering to make up for dry spells, and late autumn planting risks frost damage. On an intensive roof, saplings grow into trees that need anchorage, and a professional engineer should design the tree anchors and the safety anchors for maintenance staff.

Three cautions remain. During construction, roof access should be restricted to roofing professionals, or the membrane given temporary protection.

EFVM finds breaches in the membrane but cannot show how far moisture has spread in the insulation below; repaired areas are re-tested immediately, and a leak detection system built into the roof is strongly recommended. The installed cost of a green roof is significantly higher than that of a conventional roof.

How to get a flat roof ready for a solar array

Start with the roof, not the panels. PV should go only on roofs in good condition, with age and remaining warranty verified, ponding and flashing problems fixed first, and the surfacing, membrane and insulation strong enough for construction and maintenance traffic.

Plan walkways wide enough for two people with tools to pass, clearance so roofing can be repaired without dismantling the array, and no conduits or rack penetrations that block drainage. Hail can damage panels that are not sufficiently robust.

Two kinds of rooftop PV exist: rigid rack-mounted arrays and integrated systems adhered directly to the roof surface. Climatic conditions have limited the use of adhered systems in Canada, so rack-mounted arrays are treated as the current technology.

Should a roof be flood tested before it is covered?

Flood testing, which means plugging the drains and filling the roof with water, is not recommended for roofs. A properly built low-slope roof is positively drained and is not designed to withstand large hydrostatic pressure loads.

The standard worked example shows how quickly the weight builds on a roof basin 15 m (about 50 ft) square, sloped at 2% to a drain at its centre.

Measure Value
Water at a uniform 50 mm (2 in) depth 50 kg/m2 (10 lb/ft2), or 11,250 kg over the 225 m2 basin
Extra water held by the slope of the basin 11.25 m3, another 11,250 kg, or 50 kg/m2 averaged over the basin
Combined load About 100 kg/m2 (20 lb/ft2)
Water pressure at 50 mm (2 in) depth 0.5 kPa (about 10 psf)
Water pressure at 150 mm (6 in) depth, as over the drain sump About 1.5 kPa (31 psf)

That weight may overload a roof built close to its design load limit. The pressure is small for a well-supported membrane, but transitions and joints that rely on sealants or compression bars may fail under it, and a leak that starts cannot be stopped until all the water has drained.

A flooded roof is also hazardous to walk on, the water released when the drain plug is pulled has enough force to pull a worker's arm into the drain, and the whirlpool may damage drain and pipe connections.

Flood testing does have a place on waterproofing systems, which are built to resist substantial hydrostatic loads and are difficult to uncover later. For roofs, the non-destructive methods are far more reliable: infrared thermography, electrical capacitance (impedance) testing, nuclear moisture testing and Electric Field Vector Mapping.

The roofing design authority chooses the method. HKS Construction Ltd uses thermal imaging, the infrared method on that list, to detect hidden moisture on commercial roofs, and includes the scans in the twice-yearly inspections of its maintenance program.

What this means for a Calgary roof

Calgary sits at about 1,045 m with strong summer UV, winters below -20 C and chinook swings that put a roof through repeated freeze-thaw in one season, exactly the cycling a PMR spares the membrane.

Hail from May to September makes panel impact resistance a local concern, and frozen or saturated green roof soil adds little insulation through a Calgary winter. HKS Construction Ltd can assess your existing roof, coordinate the structural review and quote the flat roof membrane work; call (587) 225-3419.

Questions people ask

What is a protected membrane (inverted) roof?

A roof where the membrane is laid on the deck and covered by extruded polystyrene insulation and ballast, so the insulation takes the sun, weather and traffic. Only closed cell XPS meeting CAN/ULC-S701 Type 4 is accepted.

Can I put a deck or patio on my flat roof?

Yes, as a PMR with pavers as ballast or on pedestals, once a structural engineer confirms the deck can carry the ballast, the surface and the people. Soprema lists paver pedestals and SOPRA-XPS among its plaza deck components.

What is the difference between extensive and intensive green roofs?

Depth and weight. Extensive roofs have 150 mm (6 in) or less of growing medium, and intensive roofs have more than 150 mm at up to 1,464.7 kg/m2 saturated; Soprema draws the intensive line at 300 mm.

Does a green roof work in Calgary's climate?

It depends on plant choice. Plants must tolerate sun, wind, drought, frost and heavy rain, and Soprema matches sedum species to the local hardiness zone.

Can any flat roof membrane be used under a protected membrane roof?

SBS, EPDM, PVC, TPO and built-up roofing all have protected membrane specifications. What changes is the bond to the deck and the flashings: PVC and TPO must be kept off bitumen, and PVC needs a separation layer against the XPS unless it is fleece-backed.

What does rooftop solar do to a flat roof warranty?

Adding an array without the roofing contractor's or manufacturer's prior consent may raise warranty costs or void the warranty. The roofer and manufacturer should be present during installation, and the roof should be inspected afterwards.

How much weight do these systems add?

From 9.8 kg/m2 for a saturated ultra light Soprema sedum mat to 1,464.7 kg/m2 for a saturated intensive garden, plus at least 50 kg/m2 of PMR ballast and 50 kg/m2 for every 50 mm of standing water.

Ready to protect your Calgary property?